AMX NetLinx Master-Ethernet Card/Module NXC-ME260 Instruction Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
Installation and Wiring
7
NXC-ME260 NetLinx Master-Ethernet Card/Module
Installation and Wiring
This section contains information about configuring the PROGRAM port, installing NetLinx
Modules and the ME260, wiring diagrams, and pinouts for assembling cables.
Setting the Program Port DIP Switch
Baud rate settings
The Program Port DIP switch is located on the front of the Master Cards. For Modules, you must
remove the front panel to access the DIP switch.
Use this DIP switch to set the baud rate for the Program Port, according to the settings shown in the
following table. Make sure the baud rate you set matches the baud rate on your PC's COM port
before programming the Master Card. By default, the baud rate is set to 38,400 (bps). Note the
orientation of the DIP Switch and the ON position label.
Program Run Disable (PRD) mode
You can also use the Program Port DIP switch to set the Master Card to Program Run Disable
(PRD) mode according to the settings listed in the table below.
PRD mode prevents the NetLinx program stored in the Master Card from running when you power
up the Master Card. PRD mode should only be used when you suspect the resident NetLinx
program is causing inadvertent communication and/or control problems. If necessary, place the
Master Card in PRD mode and use the NetLinx Studio program to resolve the communication and/
or control problems with the resident NetLinx program. Then, download the new NetLinx program
and try again.
Baud Rate Settings
Baud Rate Position 5 Position 6 Position 7 Position 8
9600 bps OFF ON OFF ON
38,400 bps (default) OFF ON ON ON
57,600 bps ON OFF OFF OFF
115,200 bps ON ON ON ON
PRD Mode Settings
PRD Mode Position 1
Normal mode (default) OFF
PRD Mode ON
Page view 10
1 ... 10 11 12 ... 48

Comments to this Manuals

No comments