INSTALLATION GUIDE Alarm Control Panel CA10 plus (Program Version 4.7) ® GDAŃSK ca10pi_e 11/03
8 Installation Guide CA-10 plus SATEL Outputs The CA-10 plus is equipped with 6 programmable outputs: 4 high-current and 2 low-current ones. The O
Section 1 - Description of the Control Panel 9 7 - KEYPAD AUX. ALARM - the output starts on triggering the alarm by the user with the ALARM AUX funct
10 Installation Guide CA-10 plus SATEL 21 - BYPASS STATUS - the output is active when some zones are bypassed in the system. Operation of the outp
Section 1 - Description of the Control Panel 11 39 - NO GUARD CODE – the output is activated by a timer programmed as the partition control TIMER, un
12 Installation Guide CA-10 plus SATEL Three operating modes of the keypad are provided: 1) Text mode. The first line of the display shows the syst
Section 1 - Description of the Control Panel 13 Deletion of the code will not cause renumbering of the other users’ access codes. Whenever a new user
14 Installation Guide CA-10 plus SATEL arming/disarming the internal partition, while arming/disarming the internal partition only affects the zone
Section 1 - Description of the Control Panel 15 the system (e.g. troubles, start of programming mode via a telephone, activation of service mode, etc
16 Installation Guide CA-10 plus SATEL Remote Programming – DOWNLOADING In order to facilitate programming, the CA-10 plus panel is equipped with a
Section 1 - Description of the Control Panel 17 waiting for a call from the computer for four hours even when the functions of automatically answerin
WARNINGS Due to safety reasons, alarm system should be installed by qualified personnel only. Telephone terminals of the panel should be connected t
18 Installation Guide CA-10 plus SATEL Figure 1 - Diagrammatic view of control panel main board, version CA10PV
Section 2 - Installation of the Control Panel 19 The stabilized voltage of the control panel power supply is 13.6 - 13.8V and is factory set. The „D
20 Installation Guide CA-10 plus SATEL IMPORTANT: Do not connect the mains power supply and the battery, until all the remaining connections are co
Section 2 - Installation of the Control Panel 21 As the LCD keypad current consumption is larger than that of the LED keypad (particularly with activ
22 Installation Guide CA-10 plus SATEL The keypads are not be connected in parallel to one CLK signal (one partition - two keypads), with the excep
Section 2 - Installation of the Control Panel 23 GND TAMP C NO +12to detector power supply circuitCOM(detector input)Zn2 X 1,1kΩCOM(power) (input)•
24 Installation Guide CA-10 plus SATEL Connection of Signaling Devices COM OUT1 COMOUT2COM OUT3 COM OUT4 COM +KPD+12 VLIMITER2.2ALIMITER2.2ALIMITER
Section 2 - Installation of the Control Panel 25 output OUT5output OUT6DB-15fuse WTAT250V/2Ato battery "+"to mainboard AC contactto ground
26 Installation Guide CA-10 plus SATEL Connection of Voice Synthesizer Where the function of alarm messaging with voice announcements is used, a v
Section 2 - Installation of the Control Panel 27 NOTES: • Do not short or touch the serial port RS-232 pins with your fingers. • Prior to connecti
CONTENTS GENERAL DESCRIPTION OF THE CONTROL PANEL...5 TECHNICAL DESCRIPTION
28 Installation Guide CA-10 plus SATEL control panel will not start on connecting the battery alone (without the mains power connected), however, i
Section 2 - Installation of the Control Panel 29 Note: If LCD keypads are installed in the alarm system, call the FS-124 service function in each L
30 Installation Guide CA-10 plus SATEL Telephone messaging - alarm reporting. The telephone messaging function requires that the following be progr
Section 3 - Activation of Selected Functions 31 • alarm system identifier (facility number - one or more for detailed reporting from a big system )
32 Installation Guide CA-10 plus SATEL the other), the panel cannot report to both stations in the „Station 1 or Station 2” mode and will change th
Section 3 - Activation of Selected Functions 33 Modem initialization The program initializes the modem after the „MODEM” item is selected from the „C
34 Installation Guide CA-10 plus SATEL • “connection interrupted” – the control panel stopped answering the computer signals. Note: If the control
Section 4 - Programming – Service Functions 35 • keypad alarm duration - 60 seconds, • counting times of counters - 30 seconds; counter values - 0,
36 LED Keypad of digit pairs (binary). The programming consists in entering a two-digit number and confirming it with the [#] key. The control panel w
Section 4 - Programming – Service Functions 37 The × Ø keys scroll the list of the actual hierarchy level. The Ö key permits „entry” to a more detail
CONTENTS FS-13 - programming zones displayed in partition 2 keypad (BIT)...43 FS-14 - program
38 Service Functions of the LCD Keypad Key Numeric mode Text mode × deletes character before cursor changes character into previous in alphabet Ø
Section 4 - Programming – Service Functions 39 Programming of this code in the LED keypad consists in entering three pairs of hexadecimal characters
40 Functions Programming Basic Parameters will dial the number until it gets through. Only when the number has been dialed in full, the busy or no an
Section 4 - Programming – Service Functions 41 SECOND SET OF OPTIONS (for LED keypad, the LED No. 11 is blinking) No. No. LCD LED Option ON DOWNLOA
42 Functions Programming Basic Parameters FS-6 - programming entry delay, exit delay , and alarm time (DEC) The settings refer to the global times an
Section 4 - Programming – Service Functions 43 FS-11 - programming partition 4 zones (BIT) The functions FS-8 to FS-11 are used to divide the alarm s
44 Functions Programming Assignment must be separately programmed in the keypad itself (see: ¤Installation Guide for LCD Keypad; ¤Keypad Service Func
Section 4 - Programming – Service Functions 45 FS-21 - programming partition 2 options (BIT) The function defines which functions are available in th
46 Functions Programming Zone Parameters In the LCD keypad, the time is programmed directly in milliseconds from 16 to 4080 (the value is automatical
Section 4 - Programming – Service Functions 47 03 - EOL detector (one-parameter - default value) 04 - 2EOL/NC detector (two-parameter – NC detect
CONTENTS FS-70 - programming partition 2 event codes (HEX)...58 FS-71 -
48 Functions Programming Zone Parameters FS-27 - programming zone options (BIT) Each control panel zone has eight associated options which activate a
Section 4 - Programming – Service Functions 49 EXAMPLE: programming the entry delay time (alarm delay) for the following zones: zone 4 - delay
50 Functions Programming Output Parameters Functions Programming Output Parameters FS-31 - programming OUT1 output The function makes it possible to
Section 4 - Programming – Service Functions 51 30 - TIMER 31 - AUDIBLE ALARM STATUS 32 - FULL ARM STATUS 33 - ARM/DISARM/CLEAR ALARM 34 - KEYPAD A
52 Functions Programming Output Parameters EXAMPLE: programming the OUT1 output for the BURGLARY/FIRE ALARM type operation, for 5 minutes, with
Section 4 - Programming – Service Functions 53 FS-38 - programming list of zones OUT4 (BIT) The function programs the list of zones associated with t
54 Functions programming parameters of transmission to monitoring stations FS-47 - programming monitoring options (BIT) These options define how the
Section 4 - Programming – Service Functions 55 • The options 5 and 6 are only meaningful when double-character codes are reported (with 4/2 or 3/2 f
56 Functions Programming Identifiers FS-58 - programming partition 4 events identifier for station 2 (HEX) FS-59 - programming system events identifi
Section 4 - Programming – Service Functions 57 FS-61 - programming zone tamper alarm codes (HEX) The codes programmed with this function are reported
CONTENTS FS-128- zones bypassed on no exit from partition 2 (BIT)...69 FS-129-
58 Functions Programming Zone Event Codes No. LCD LED Option ON send ZONE ALARM code 1 OFF do not send ZONE ALARM code ON send ZONE TAMPER ALARM
Section 4 - Programming – Service Functions 59 show the programmed code (1 to 4 the first character, 5 to 8 the second character of the code). The LE
60 Functions Programming System Event Codes Functions Programming System Event Codes Apart from the events from zones and partitions, the CA-10 plus
Section 4 - Programming – Service Functions 61 • The code 4 is recorded in the event log when lack of communication with the station lasted so long
62 Functions Programming Dialer FS-88 - programming telephone number 2 (HEX) FS-89 - programming telephone number 3 (HEX) FS-90 - programming telepho
Section 4 - Programming – Service Functions 63 FS-96 - programming message 1 (POLPAGER format) FS-97 - programming message 2 (POLPAGER) FS-98 - progr
64 Functions Programming Dialer which cannot be reached (when nobody answers the call or the panel receives the busy signal all the time, etc.). The
Section 4 - Programming – Service Functions 65 The programming consists in entering four characters from 0 to B (twice two characters), the first cha
66 Special Functions • MASTER code, partition 3 = 3456 • MASTER code, partition 4 = 4567. FS-111 - programming keypad addresses (BIT) The keypads
Section 4 - Programming – Service Functions 67 • start the DLOAD10 program on the computer and select the number of communication port (COM); • ca
GENERAL DESCRIPTION OF THE CONTROL PANEL The CA-10 plus alarm control panel is a new version of the hitherto manufactured CA-10. The changes, as com
68 Special Functions messages. If parameters of such signals change, it will be sufficient to specify new data. The programming consists in entering
Section 4 - Programming – Service Functions 69 Additional Functions Extra functions, which were added in the process of developing the functional fea
70 Additional Functions Option 1 refers to disabling the hardware access to the service mode. If this option is selected, it is only possible to enter
Section 4 - Programming – Service Functions 71 Option 1 disables the possibility of arming, if the control panel has detected a battery trouble. When
72 Additional Functions which will be sent, occurs in the system, the control panel will start counting the time again. This feature can be disabled b
Section 4 - Programming – Service Functions 73 Note: Similarly as in other SATEL control panels, shorting the pins and powering up alone will not
74 DLOAD10 After opening the „Modem” window, select the corresponding modem type or click on the „! Change” button to enter data according to the
Section 5 - Remote Programming 75 The modem communication can be started by clicking on the icon (or selecting the „MODEM” command from the „COMM
76 Appendix A – Table of HEX Characters Appendix A Table of HEX characters Decimal format (DEC) Binary format (BIN) Hexadecimal format (HEX) State
Appendix B - Signaling 77 Appendix B States signaled with LEDs LEDs 1 to 12: • off - zone free (not violated) • on - zone violated • on with a
6 Installation Guide CA-10 plus SATEL TECHNICAL DESCRIPTION OF THE CONTROL PANEL Zones In its basic configuration, the CA-10 plus control panel ha
78 States signaled States signaled with sound The signals produced to confirm the operation on the keypad: • three short - system arming/disarming
Appendix C - Technical Data 79 Appendix C TECHNICAL DATA Control panel supply voltage... AC 230(+10%; -15%
80 Appendix C - Technical Data Table 1. Example of panel power supply load estimation and battery selection. No. Loads Max current Mean current
CA-10 plus Alarm System - Connection Diagram (detailed description of main board terminals - see p. 17-18). +12 CLK DATA Z1 COM Z2Partition 1 ke
History of the Manual Updates The updates below refer to the manual for the control panel with program version 4.0. Date Program version Descripti
Section 1 - Description of the Control Panel 7 keypad and will send a “zone alarm” code. It is intended for connecting detectors not related to the b