Design Guidelines & Procedures Version 18 ©
Electrical Services Section 20.00 / Page 1
20.00 Electrical Services
The requirements of this Section are generally Mandatory (Refer to Section 1.00)
20.01 General Requirements
This section outlines the University's minimum requirements for electrical services.
The layout of luminaires and power outlets should allow flexibility such that spaces can be
subdivided into separate areas.
Where island rooms exist, these shall be conduited to allow for the installation of power and
communication outlets from the relevant sub-board or Telecommunication Equipment Room
(TER) where these are not installed in the first instance.
20.02 Lighting
20.02.01 Performance Guidelines
All internal and external lighting shall be designed to enhance safe movement, personal safety
and security (CPTED), refer to Section 2.00 Planning & Design Controls. The following
lighting categories, in accordance with AS 1158.3.1 shall apply to the following nominated
external areas;
Bus stops P6
Areas adjacent to entry/exit (5m radius) P10
General grounds used for night activity P7
General grounds adjacent to areas used for night activity P8
Entrapment spots P10
Internal areas shall be designed in accordance with AS 1680 and shall also incorporate the
requirements of AS 1428.
Lighting levels for each area shall be nominated by the Consultant or Contractor and submitted
for approval as part of Schematic Design. Over illumination is discouraged.
Particular areas nominated for specialised requirements will be identified by the user in the SDFs
and the appropriate lighting quality and levels recommended.
20.02.02 Design Requirements
Luminaires – All luminaires shall be manufactured from Australian made components where
possible and be approved by the Electricity Authority. All luminaires shall be supplied complete
with lamps and fused terminal blocks. Spring loaded ‘tombstone’ lamp holders shall not be used.
Single lamp luminaires generally shall be installed, however dual lamp luminaires may be used
where high ceilings occur or high lighting levels are required.
Fluorescent luminaires shall be of the high efficiency type incorporating high frequency warm/soft
start ‘Osram’, ‘Tridonic Atco’ or approved equal electronic ballasts, with a suitable controller as
outlined in Clause 20.03 of this Section.
All luminaires shall be adequately ventilated. Temperature rise in the fittings should be restricted
to 50
o
C above ambient.
Diffusers shall be integral to the luminaire and easily removable. All components shall be easily
accessible, with the luminaire in-situ. Fittings which have to be dismantled in order to replace
diffusers, lamps or tubes shall not be used.
Diffusers to T8 single lamp luminaires shall be;
K12 diffuser for common areas
K19 diffusers for offices, computer rooms and seminar rooms
Page view 0
1 2 ... 26

Summary of Contents

Page 1 - 20.00 Electrical Services

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 1 20.00 Electrical Services The requirements of

Page 2

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 10 20.07.02 Access Control Two (2) dual 10A

Page 3

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 11  1 No. in the ceiling space within 300mm of

Page 4 - 20.03 Lighting Control

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 12 In cases where a UPS is required, the wiring

Page 5

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 13 Non-fading laminated prints of the ‘As Constr

Page 6

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 14 each of the main building services emanating

Page 7

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 15 An A1 size non-fading laminated single line c

Page 8

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 16 20.08.12 Workshop Drawings Detailed constr

Page 9 - 20.07 Power

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 17 All cable trays, ladders and ducts shall have

Page 10

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 18 Cables shall not be installed within the ceil

Page 11

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 19 The master controller and communication netwo

Page 12

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 2 Installation of luminaires with a T5 lamp sha

Page 13

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 20 20.13 Lightning Protection Lightning prote

Page 14

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 21 Mt Gravatt - Simplex Model 2320 situated in R

Page 15

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 22 20.16 High Voltage System Consideration s

Page 16 - 20.10 General Wiring

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 23 20.18 Electrical Design Requirements The

Page 17

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 24 20.19 Deliverables Section No. Deliver

Page 18

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 25

Page 19

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 26 Appendix B METER INSTALLATION RECORD MET

Page 20 - 20.14 Clocks

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 3 conductive material support system such as ‘Ez

Page 21

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 4 Luminaires shall not be mounted above stairs a

Page 22 - 20.17 Testing

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 5 An electronic copy of the lighting program, an

Page 23

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 6 The interface between the AMX system and the

Page 24 - 20.19 Deliverables

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 7 Table 2 : Typical Lighting Programs continued

Page 25

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 8 20.03.06 Fire Alarm Interface Lecture Theat

Page 26 - METER INSTALLATION RECORD

Design Guidelines & Procedures Version 18 © Electrical Services Section 20.00 / Page 9 20.05 Particular Lighting Requirements for O