Dimmer Switch Remote
Switch
Remote
Dimmer
Installation Instructions
Please Read Before Installing
Multigang Installations
In multigang installations, several controls are grouped
horizontally in one multigang wallbox.
When combining controls in a wallbox, derating is
required; however, no derating is required for remote
dimmers / switches.
Derating Chart
Control Load Type End of
Gang
Middle
of Gang
-6D
Incand. 500 W 400 W
MLV
400 W /
500 VA
300 W /
400 VA
-6NA
Incand./ ELV 500 W 400 W
MLV
400 W /
500 VA
300 W /
400 VA
-10D,
-10ND
Incand. 800 W 650 W
MLV
600 W /
800 VA
500 W /
650 VA
-F6AN-DV*
3-wire
Fluorescent/
LED
5 A 3.5 A
50
ballasts
35
ballasts
-8ANS
Lighting 6.5 A 5 A
Motor
1/4 HP
5.8 A
1/6 HP
4.4 A
-8S-DV
Lighting
8 A
(2-gang)
7 A
(3-gang)
7 A
Motor
1/10 HP
3 A
* The maximum load for the -F6AN-DV is either the derated load or
the number of ballasts, whichever is LESS.
Note: -8ANS, -RD-277 and -RS-277 controls have fins
that need to be removed for multigang installations.
-6D, -6NA, -10D, -10ND, -F6AN-DV, -8S-DV, -RD and
-RS controls do not have fins that need to be removed
for multigang installations.
Troubleshooting Guide
Lutron Electronics Co., Inc.
7200 Suter Road | Coopersburg, PA 18036-1299
P/N 044-312 Rev. A 03 / 2012
Important Notes
WARNING – Entrapment Hazard –
To avoid the risk of entrapment, serious
injury, or death, these controls must
not be used to control equipment which is not
visible from every control location or which
could create hazardous situations such as
entrapment if operated accidentally. Examples
of such equipment which must not be operated
by these controls include (but are not limited
to) motorized gates, garage doors, industrial
doors, microwave ovens, heating pads, etc. It
is the installer’s responsibility to ensure that the
equipment being controlled is visible from every
control location and that only suitable equipment
is connected to these controls. Failure to do so
could result in serious injury or death.
Codes: Install in accordance with all local and
national electrical codes.
Grounding: When no “grounding means” exist
in wallbox, the 2011 National Electrical Code
®
(NEC
®) allows a control to be installed as a
replacement if 1) a nonmetallic, noncombustible
faceplate is used with nonmetallic attachment
screws or 2) the circuit is protected by a ground
fault circuit interrupter (GFCI). When installing
a control according to these methods, cap or
remove green wire before screwing control into
wallbox.
Neutral Wire: -6NA, -10ND, -8ANS and
-F6AN-DV require a neutral wire connection
in the wallbox where the dimmer/switch is to
be installed. If a neutral wire connection is not
available in the wallbox, contact a licensed
electrician for installation.
Environment: Ambient operating temperature:
32°F to 104°F (0°C to 40°C), 0% to 90%
humidity, non-condensing. Indoor use only.
Spacing: If mounting one control above
another, leave at least 4
½
in (114 mm) vertical
space between them.
Wallplates: Lutron
® Claro® and Satin Colors®
wallplates are recommended for best color
match and aesthetic appearance. Do not paint
controls or wallplates.
Cleaning: To clean, wipe with a clean damp
cloth. DO NOT use any chemical cleaning
solutions.
Wallboxes: Lutron recommends using 3
½
in
(89 mm) deep wallboxes for easier installation.
Several controls may be installed in one
multigang wallbox. See Derating Chart.
Remote Dimmers / Switches: Use only remote
dimmers (CCD-RD / CCD-RD-277) and remote
switches (CCD-RS / CCD-RS-277)
with dimmers /switches. Up to 9 CCD-RD /
CCD-RD-277 or CCD-RS /CCD-RS-277 may
be used with controls. Mechanical 3- or 4-way
switches will not work.
RF Device Placement: RF dimmers /switches
must be located within 30 ft (9 m) of an RF
Signal Repeater. Remote dimmers / switches
are not required to be within a specific range
of a repeater.
For systems with an RF signal repeater,
RF dimmers / switches cannot be controlled
by the system until they are programmed in
a system.
English
Lutron, Claro, Satin Colors, Maestro, Hi-lume, Ecosystem, Eco-10, and ) are registered trademarks and Clear Connect, Hi-lume 3D, Compact SE, and FASS are trademarks of Lutron Electronics Co., Inc.
NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.
©2012 Lutron Electronics Co., Inc.
Mounting Diagram
Control
Mounting
Screws
Wallbox
Control
Included:
Wire Connectors (1 or 5)
Mounting Screws (2)
Adapter
Mounting
Screws
Wallplate adapter and
wallplate purchased
separately.
Wallplate
Adapter
Wallplate
Technical Assistance:
U.S.A. / Canada: 1.800.523.9466 | Mexico: +1.888.235.2910
Brazil: +55 (11) 3257-6745 (M-F 8:30 to 17:30 BRT) | Other Countries: +1.610.282.3800
24 hours a day, 7 days a week www.lutron.com
* Typical Power Consumption test conditions:
Dimmer / Switch: load is off, nightlight mode enabled.
Remote Dimmer / Switch: load is off.
WARNING – Shock Hazard –
To avoid the risk of electric shock
locate and remove fuse or lock
circuit breaker in the OFF position before
proceeding. Wiring with power ON could
result in serious injury or death.
1. Turn power OFF at fusebox or circuit
breaker.
2. Check the installation for short circuits
before installing control(s). With power
OFF, install standard mechanical
switch(es) between Hot and load.
Restore power. If lights do not work or
a breaker trips, check wiring. Correct
wiring and check again. Install control(s)
only when short is no longer present.
Warranty is void if control is turned ON
with a shorted circuit.
3. Wire controls according to one of the
following options:
a. Terminals: Trim or strip wallbox wires
to the length indicated by the strip
gauge on the back of the control.
• Push-In Terminals: Use
with 14 AWG (1.5 mm
2
)
solid copper wire only.
Do NOT use stranded or
twisted wire.
Insert wires fully. To
release wire, insert small,
flat screwdriver into slot
below push-in terminal.
Push screwdriver in while
pulling wire out.
OR
Each control
has inside fins
removed
Control at middle
of gang has all fins
removed
Do Not remove outside fins on
controls at the end of gang
Single Location Installation
1
without Neutral
-6D, -10D (120V~)
Wiring Diagram 1
Brass
Black
Blue
1
Green
Ground
Hot/Live
Neutral
Load
Dimmer
120 V~
50/60 Hz
Load Specifications:
Control Load Type Min. Load Max. Load
-6D
1
Incand. 50 W 600 W
MLV
2
50 W / VA
450 W /
600 VA
-6NA
1
Incand./
ELV
2
5 W 600 W
MLV
2
5 W / VA
450 W /
600 VA
-10D
1
Incand. 50 W 1000 W
MLV
2
50 W / VA
800 W /
1000 VA
-10ND
1
Incand. 10 W 1000 W
MLV
2
10 W / VA
800 W /
1000 VA
-F6AN-DV
3, 4, 5
3-wire
Fluores-
cent/ LED
0.05 A 6 A
1 ballast 60 ballasts
-8ANS
6
Lighting 10 W / VA 8 A
Motor 0.08 A
1/4 HP
5.8 A
-8S-DV
7, 8
Lighting 40 W / VA 8 A
Motor 0.4 A
1/10 HP
3 A
-RD
9
See Dimmer
8.3 A
-RS
9
See Switch
-RD-277
10
See Dimmer
-RS-277
10
See Switch
1 Dimmer Load Type: -6D, -10D and -10ND are designed
for use with permanently installed incandescent, magnetic
low-voltage, or tungsten halogen only.
-6NA is designed for use with permanently installed
incandescent, electronic low-voltage, magnetic low-voltage,
or tungsten halogen only.
Do not install dimmers to control receptacles or motor-
operated appliances. Do not mix incandescent, halogen,
MLV, or ELV load types on a dimmer.
2 Low-Voltage Applications: Use -6D,-10D and -10ND
with magnetic (core and coil) low-voltage transformers
only. Not for use with electronic (solid-state) low-voltage
transformers.
Use -6NA with dimmable electronic (solid-state) or
magnetic (core and coil) transformers.
Operation of a low-voltage circuit with lamps inoperative
or removed may result in transformer overheating and
premature failure. Lutron strongly recommends the
following:
a. Do not operate low-voltage circuits without operative
lamps in place.
b. Replace burned-out lamps as quickly as possible.
c. Use transformers that incorporate thermal protection or
fused transformer primary windings to prevent transformer
failure due to overcurrent.
3 Fluorescent Dimmer Load Type:
-F6AN-DV is designed for use with permanently installed
3-wire 120V~ or 277V~ line voltage control fluorescent
ballasts or LED drivers. Use only with Hi-lume
®, Hi-lume®
3D, Hi-lume
® A-Series, CompactSE
™
, Eco-10®, or
EcoSystem
® (H3D-, FDB-, ECO-, HL3-, EC5-, L3D). Do
NOT use with any other ballasts or drivers. Do not install to
control receptacles or motor-operated appliances.
4 Power Boosters / Load Interfaces: -6NA, -10ND, -F6AN-
DV, and -8ANS can be used to control power boosters /
load interfaces. For a list of compatible power boosters /
load interfaces see www.lutron.com
5 Maximum Load: The maximum load for the -F6AN-DV is
either the derated load or the number of ballasts, whichever
is LESS.
6 Switch Load Type -8ANS: -8ANS is designed for use with
permanently installed 120V~ incandescent, magnetic
low-voltage, electronic low-voltage, or fluorescent loads
and with motor loads up to 1/4HP (5.8A).
7 Switch Load Type -8S-DV: -8S-DV is designed for use
with permanently installed 120V~ incandescent, magnetic
low-voltage, electronic low-voltage, fluorescent, or motor
loads; or 277V~ magnetic low-voltage or fluorescent
loads.
8 Shunt Capacitor (included): Some -8S-DV installations
may require the use of a shunt capacitor. This is especially
necessary for load types sensitive to leakage current
(i.e. fluorescent ballasts). If load flickers, install a shunt
capacitor. For shunt
capacitor installation see Wiring
Diagram 4 or 8.
9 120 V~ Remote Dimmer / Switch: -RD and -RS are
designed for use with 120V~ dimmers / switches.
10 277 V~ Remote Dimmer / Switch: -RD-277 and -RS-277
are designed for use with 277V~ dimmers / switches. Do
NOT use with motor loads.
1
When using controls in single location installations, tighten the blue terminal without any wires attached.
DO NOT connect the blue terminal to any other wiring or to ground.
2
Shunt capacitor must be installed inside the load fixture or in a separate J-box.
3
Install only 1 dimmer / switch per circuit. Up to 9 remote dimmers / switches may be connected to a
dimmer / switch. Total blue terminal wire length may be up to 250 ft (76 m).
4
Neutral wire dimmers / switches must be connected on the Load side of a multi-location installation.
Lamp Replacement
WARNING – Shock Hazard – For
any procedure other than routine
lamp replacement, power must be
disconnected at the main electrical panel.
Working with power ON could result in
serious injury or death.
For your safety during routine lamp
replacement, remove power from the
fixture(s) by moving the FASS
TM switch into
the OFF position on the dimmer / switch
and all remote dimmers / switches.
Symptom Probable Cause and Action
Lights don’t turn ON / OFF
when tapswitch on
dimmer / switch or remote
dimmer / switch is pressed
Power not present
• Circuit breaker OFF or tripped. Perform short circuit check.
• FASS
™
is in the OFF position. Move FASS
™
to the ON position. Check
the dimmer / switch and all of the remote dimmers / switches. See Lamp
Replacement.
Wiring
• Wires shorted. Make sure the blue terminal is not grounded or shorted to
any other wires.
• Wiring error. Check wiring to be sure it agrees with installation instructions
and wiring diagrams.
• For -8S-DV, increase load to meet the appropriate minimum load
requirement or use shunt capacitor or-8ANS. See Load Specifications.
Load is less than minimum load requirement
• Make sure the connected load meets the appropriate minimum load
requirement for that control. See Load Specifications.
• For -8S-DV, increase load to meet the appropriate minimum load
requirement or use shunt capacitor or -8ANS. See Load Specifications.
Lamps burned out or not installed
• Replace or install lamps.
Dioded lamps
• If dioded lamps are being used, replace with non-dioded lamps.
Load flickers or tapswitch
does not work even if load
is greater than 40 W (-8S-
DV only)
Leakage current
• Install a shunt capacitor. See Wiring Diagram 4 or 8.
Light turns ON and OFF
continuously or lights turn ON
when tapswitch is pressed,
then turn OFF
Load does not meet the minimum load requirement
• Increase load to meet the appropriate minimum load requirement for that
control. See Load Specifications.
• Install a shunt capacitor with -8S-DV. See See Wiring Diagram 4 or 8.
• For -8S-DV, increase load to meet the appropriate minimum load
requirement or use shunt capacitor or -8ANS. See
Load Specifications.
Load flickers
(-8S-DV only)
Load does not meet the minimum load requirement
• Increase load to meet the appropriate minimum load requirement for that
control. See Load Specifications.
• Install a shunt capacitor. See Wiring Diagram 4 or 8.
Lights don’t turn ON/OFF
from a keypad
Improper programming
• Program according to the system setup guide.
Out of RF range
• Reposition to be within 30 ft (9 m) of an RF signal repeater.
Wiring
• Wires shorted. Make sure the blue terminal is not grounded or shorted to
any other wires.
• Wiring error. Check wiring to be sure it agrees with installation instructions
and wiring diagrams.
Wallplate is warm Solid-state control dissipation
• Solid-state dimmers / switches internally dissipate about 2% of the total
connected load. It is normal for dimmers /switches to feel warm to the
touch during operation.
Single Location Installation
1
without Neutral
-8S-DV with optional shunt capacitor
2
(120-277V~)
Wiring Diagram 4
Brass
Black
Blue
1
Green
Ground
Hot/Live
Neutral
Load
Switch
120-277 V~
50/60 Hz
Shunt
Capacitor
2
Optional
Single Location Installation
1
with Neutral
-F6AN-DV (120/277V~)
Wiring Diagram 3
Brass
Black
Blue
1
Green
Ground
Hot/Live
Neutral
Lutron® Ballast /
LED Driver
Lutron® Ballast /
LED Driver
Dimmer
120/277 V~
50/60 Hz
Black
Orange
White
Orange
Silver
Black
Orange
White
Multi-Location Dimmer Installation
3
with Neutral
4
-F6AN-DV with -RD or -RD-277
(120/277V~)
Wiring Diagram 7
Dimmer
Remote DimmerRemote Dimmer
Note: Dimmer must be installed on the
load side of the circuit.
Brass/
Red
Brass/
Red
Black
Blue
Green
Ground
Hot/Live
Neutral
Lutron® Ballast /
LED Driver
120/277 V~
50/60 Hz
Black
Orange
White
Black
Orange
White
Lutron® Ballast /
LED Driver
Brass
Black
Blue
Green
Ground
Orange
Silver
Black
Blue
Green
Ground
Status LEDs (Dimmer only)
Indicate light level; glows softly
as night light when load is off
Tapswitch
Tap on/off
Dimming Rocker
Press to Brighten
Press to Dim
FASS
™
Front
Accessible
Service
Switch
Dimmer Operation
Switch Operation
Status LED (Switch only)
Indicates light status; glows softly
as night light when load is off
Tapswitch
Tap on/off
FASS
™
Front
Accessible
Service
Switch
OR
-RD-277 or
-RS-277 only
OFF ON
Note: Dimmer must be
installed on the load side of
the circuit.
Multi-Location Installation
3
with Neutral
4
-6NA and -10ND with RD-RD, and -8ANS with RD-RS (120V~)
Brass
Silver
Black
Blue
Green
Ground
Load
Brass
Black
Blue
Green
Ground
Remote Dimmer/
Remote Switch
120 V~
50/60 Hz
Brass
Black
Blue
Green
Ground
Hot/Live
Neutral
Remote Dimmer/
Remote Switch
Dimmer /
Switch
Wiring Diagram 6
Single Location Installation
1
with Neutral
-6NA, -10ND, and -8ANS (120V~)
Wiring Diagram 2
120 V~
50/60 Hz
Brass
Silver
Black
Blue
1
Green
Ground
Hot/Live
Neutral
Load
Dimmer/Switch
• Screw Terminals: Use
with 12 AWG (2.5 mm
2
) or
14 AWG (1.5 mm
2
) solid
copper wire only. Do NOT
use stranded or twisted
wire.
Wrap wire around screw
terminal. Tighten securely
to 5 in-lb (0.55 N
•
m).
b. Wire Connectors:
Prepare wires. When making wire
connections, follow the
recommended strip lengths
and combinations for the
supplied wire connector.
Note: Wire connectors
provided are suitable for
copper wire only.
Wire Connector:
•
Strip insulation 3/8 in (10 mm) for 14 AWG
(1.5 mm
2
) or 12 AWG (2.5 mm
2
) wire.
• Strip insulation 7/16 in (11 mm) for
18 AWG (0.75 mm
2
) or 16 AWG
(1.0 mm
2
) wire.
•
Use to join one or two 14
AWG (1.5
mm
2
)
or 12AWG
(2.5 mm
2
) wires with one
18AWG (0.75mm
2
) or 16AWG
(1.0mm
2
) wire.
For single and multi-location installations
see Wiring Diagrams.
4. Push all wires back into the wallbox and
loosely fasten the control to the wallbox
using the control mounting screws
provided. Do not pinch the wires.
5. Attach the Lutron
® Claro® or Satin
Colors
® wallplate adapter and wallplate.
See Mounting Diagram.
a. Install wallplate adapter onto front of
control(s).
b. Tighten control mounting screws until
wallplate adapter is flush to wall (do
not over-tighten).
c. Snap wallplate onto wallplate adapter,
and verify that control is aligned
properly.
d. If controls are misaligned, loosen
mounting screws appropriately.
6. Restore power. Verify correct local
operation. See Dimmer Operation or
Switch Operation.
Twist wire
connector tight.
Installation
Warranty: For warranty information, please see the enclosed Warranty, or visit
www.lutron.com/resiinfo
Multi-Location Installation
3
without Neutral
-6D, -10D with -RD (120V~)
Wiring Diagram 5
Brass
Black
Blue
Green
Ground
Load
Dimmer
/
Remote Dimmer
3
Brass
Black
Blue
Green
Ground
Remote Dimmer
/
Dimmer
3
Brass
Black
Blue
Green
Ground
Hot/Live
Neutral
Remote Dimmer
/
Dimmer
3
120 V~
50/60 Hz
Note: Dimmer may be installed in any
location in the circuit.
Returning Dimmers / Switches to Factory Settings
Note: Returning a dimmer / switch to its factory settings will remove it from the system and erase all programming
from it.
Step 1 : Triple tap the tapswitch on a control. DO NOT release after the third tap.
Step 2 : Keep the tapswitch pressed on the third tap (for approximately 3 seconds) until the LEDs on the dimmer
start to scroll up and down quickly, or the LED on the switch flashes quickly
Step 3 : Release the tapswitch and immediately triple tap the tapswitch again. The LEDs on the dimmer will scroll
up and down slowly. The LED on the switch will flash slowly.
The control has now been returned to factory settings and needs to be reprogrammed into a system.
Multi-Location Installation
3
without Neutral
-8S-DV with -RS or -RS-277 and optional shunt capacitor
2
(120–277V~)
Black
Blue
Green
Ground
Load
Switch / Remote
Switch
3
Black
Blue
Green
Ground
Remote Switch /
Switch
3
Brass/
Red
Black
Blue
Green
Ground
Hot/Live
Neutral
Remote Switch /
Switch
3
Note: Switch may be installed in any
location in the circuit.
Shunt
Capacitor
2
120–277 V~
50/60 Hz
Optional
Wiring Diagram 8
Brass/
Red
Brass/
Red
Dimmer:
CCD-6D, -6NA, -10D, -10ND
(120V~ 50 / 60 Hz)
CCD-F6AN-DV (120/277V~ 50 / 60 Hz)
Switch: CCD-
8ANS
(120V~ 50 / 60 Hz)
CCD-8S-DV (120-277V~ 50 / 60 Hz)
Typical Power Consumption*: 0.6 W
Remote Dimmers:
CCD-RD (120
V~
50 / 60 Hz)
CCD-RD-277 (277
V~
50 / 60 Hz)
Remote Switches:
CCD-RS (120
V~
50 / 60 Hz)
CCD-RS-277 (277
V~
50 / 60 Hz)
Typical Power Consumption*: 0W