ViewStat Installation and Wiring
10
ViewStat Communicating Thermostat
Attaching the MiniVerter to the ViewStat
Before attaching the MiniVerter to the rear of the ViewStat, connect the wiring, as described below:
1. Detach the faceplate from the base of the ViewStat.
2. Pull the stripped/tinned wires through the cutout in the center of the base (FIG. 5).
Before mounting the ViewStat, you must attach the MiniVerter to the rear panel of the ViewStat, as described
below:
1. Detach the faceplate from the base of the ViewStat.
2. Pull the stripped/tinned wires through the cutout in the center of the base (FIG. 5)
3. Connect the communications wiring:
a. Blue to B-
b. Orange to B+
c. Red/White to A-
d. Black/White to A+
4. Connect the power wiring:
a. Black to C
b. Red to R
5. Install a jumper from RH to RC.
6. Insert the MiniVerter (connector-side first) into the guide-slots located on the bottom of the MiniVerter
mounting bracket (FIG. 6).
7. Slide the MiniVerter back into its locking position in the mounting bracket.
8. With the connector-side of the MiniVerter seated in the guide-slots, gently press the opposite side of the
MiniVerter in and down, to snap it into its locked position on the mounting bracket.
FIG. 5 ViewStat base with Communication, Power and Equipment terminals
ommon
ac
from 24 VAC
HVAC System
Power (red)
from 24 VAC
HVAC System
jumper
from RC
to RH
from Miniverter
Communication
Terminal
cutout
Equipment
terminal
Power
Ter min a l
Comments to this Manuals