Installation Sheet
RDM-HDC Heavy Duty DC Module
2400 W, 0-12 VDC
The RDM-HDC Heavy Duty DC Module is a heavy-duty 2400 W module for
dimming of fluorescent ballast loads. It uses a 0 to 12 VDC current sinking
or sourcing for use with all four-wire ballasts. It is designed for use with the
RDA series of enclosures, in an AMX Lighting™ modular digital dimming
system. The module’s 120, 240, and 277 VAC ratings are CE, UL, and
C-UL approved.
RDM-HDC UL and C-UL Ratings
120 VAC, 50/60 Hz, 2400 W
240/277 VAC, 50/60 Hz, 2400 W
Control Out: 50 mA, 12 VDC
sourcing/sinking
Suggested Dimmed Loads
Four-wire dimmable ballasts
All low-voltage DC controlled ballasts
Specifications
Dimensions (HW): 10" x 2.75" (25.4 cm x 6.99 cm)
Non-phase dependant
Use wires rated at 75°C (167°F)
Torque terminals to 20 in-lbs. (2.3 N/M)
Max. wire size: 10 AWG (4 mm²)
Wire stripping length: 0.28" (7 mm)
Weight: 1.3 lbs. (0.590 kg)
BTU/hr: 150
Control current: 150 mA @ 12 VDC
Caution: Pre-Installation Notes
All Class 1 wiring must be connected to proper terminals.
All control wiring must be connected to proper terminals.
Disconnect power while installing or connecting the unit.
Keep top and bottom air vents clear at all times.
Use low-voltage wires with a 300 volt rating or greater.
Use field installed copper conductors.
All electrical ratings are for continuous duty.
For indoor use only.
Test loads for shorts before connecting.
This module may require extra power from the AXlink connection or an
external power supply connected to the control card.
Connecting the RDM-HDC to the AMX Lighting Master
Lighting Application Drawings
Warning: Failure to ground the ballast may cause ballast
failure
FIG. 1 RDM-HDC
Low-voltage control
wiring: 4-pin
Relay
+ out (LV)
- out (LV)
Neutral
Line in
Load
High
Low-voltage
voltage
connector to AMX
Lighting master
controller
Mounting
points
FIG. 2 Connecting the RDM-HDC and AMX Lighting Master
FIG. 3 RDM-HDC application wiring
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
RDM-HDC 4-pin module connector
1 (+)
2 (DIM)
3 (-)
GND
4-pin plug from RDM series module
Note: The 4-pin plugs from the module connector to the 4-pin
connector on the master (black plug cover facing up).
RDM-HDC
LOAD LINE NEUT CON
Ballast
Florescent Ballast
Neutral
Line in (HOT)
Load
Neutral
+
-
Low-voltage wire rated
to 300 V
Circuit breaker
panel